Why does a power plant need that much circuitry in the first place? I get that it’s probably super-old and probably built back when you needed a whole server rack for the equivalent compute of a pocket calculator (and also it’s relatively bulky because it’s a lot of relays for switching high-current stuff), but still, a coal power plant shouldn’t be that complicated, right?
I’ve been in more than few power plants including nukes. There is wiring everywhere for process control and instrumentation.
It’s about IO not compute. The controllers for plants like this aren’t very complicated but they can have many thousands of signals going to/from them. For a ~500MW plant I’d expect somewhere between 2-5k IO, more if it’s nicely automated.
Automation engineer, have worked on power plants.
Having less compute may mean even more cables: rather than having data sent over one cable then decoded, each line is either on or off, controlling: something… (there could be signals here just contemplating). In modern stuff the logic is condensed, with data running between, in effect these older systems were one distributed logic unit. Probably over simplifying hut think of an old motorcycle, many cables, because you have to run power and ground back and forth all the way from switches to lights motors etc and back again.
Right, but even taking that into account, how many control signals could the thing possibly need?
If I enumerate every possible signal I can think of that a coal plant might need (boiler temp, fire temp, turbine speed, water flow, fuel hopper door control, etc.), and then arbitrarily multiply by an order of magnitude, my estimate is still lower than the number of wires I see in the pic.
I’d take each of your metrics and multiply it by 10, and then multiply it by another 10 for everything you haven’t thought about, then probably double it for redundancy.
Because “fire temp” is meaningless in isolation. You need to know the temperature is evenly distributed (so multiple temperature probes), you need to know the temperature inside and the temperature outside (so you know your furnace isn’t literally melting), you need to know it’s not building pressure, you need to know it’s burning as cleanly as possible (gas inflow, gas outflow, clarity of gas in, clarity of gas out, temperature of gas in, temperature of gas out, status of various gas delivery systems (fans (motor current/voltage/rpm/temp), filters, louvres, valves, pressures, flow rates)), you need to know ash is being removed correctly (that ash grates, shakers, whatever are working correctly, that ash is cooling correctly, that it’s being transported away etc).
The gas out will likely go through some heat recovery stages, so you need to know gas flow through those and water flow through those. Then it will likely be scrubbed of harmful chemicals, so you need to know pressures, flow rates etc for all that.
And every motor will have voltage/current/rpm/temperature measurements. Every valve will have a commanded position and actual position. Every pipe will have pressure and temperature sensors.The multiple fire temperature probes would then be condensed into a pertinent value and a “good” or “fault” condition for the front panel display.
The multiple air inlet would be condensed into pertinent information and a good/fault condition.
Pipes of a process will have temperature/pressure good/fault conditions (maybe a low/good/over?)And in the old days, before microprocessors and serial communications, it would have been a local-to-sensors control/indicator panel with every reading, then a feed back to the control room where it would be “summarised”. So hundreds of signals from each local control/indicator panel.
Imagine if the control room commanded a certain condition, but it wasn’t being achieved because a valve was stuck or because some local control over-rode it.
How would the control room operators know where to start? Just guess?
When you see a dangerous condition building, you do what is needed to get it under control and it doesn’t happen because…
You need to know why.Wow learned a lot from this makes the exploring abandoned power station videos more fun, thanks!
For one, redundant systems. For another, lots of sensors. Electric generation also has a whole lot of important things going on that take tons of cabling. Burning the coal is the easy part. Grid phase alignment and a host of other fun things need to happen quickly and in a coordinated way with failovers and data lines to multiple separate places.
Where? 500000 of us would LOVE to take over such a location, free of charge… That’s how I know this shit is total BS.
Please sir can I see some more?
It’s giving me Eldritch horror vibes.
Am I the only one considering the amount of copper in this room? Is this the Detroit in me run amuck?
I was thinking gold but same, brother, same

OP is right that is a big job.
That was my first thought. Unless some of these runs are fiber there’s a ton of copper. Generally you don’t see “wire” and “abandoned” in the same photograph.
So much effort goes into things so temporary.
And so much effort will go into burying them rather than reclaiming them.
I see the server room of my last job wasn’t that bad at all.
Oh this here is my shit. You should see some of the steel mills we’ve worked on. Panels so old they just screwed them right into the stone walls, live busbars bent and snaking around in open air, fuck all for controls. Love it.
Imagine troubleshooting that.
I’m surprised no-one has stripped out all that wire for scrap.
It was probably abandoned because the internet went out in one of the rooms and they figured itd be easier to build a new plant than deal with this mess.